The same generator set carries two or three numbers on its data sheet. Comparing quotes on the wrong one is the most common reason one offer looks 10% cheaper than another.
The maximum power for emergency use when the grid fails. Typically limited to about 200 hours a year, with no overload allowed. Under ISO 8528 the average load over 24 hours should not exceed about 70% of the standby rating.
Power available for an unlimited number of hours a year at variable load, with a 10% overload allowed for one hour in twelve. This is the rating to use when the generator is your main supply: mines, remote sites, rental, construction.
Constant 100% load for unlimited hours, used mainly for base-load power plants. Less common in quotations.
For most diesel sets, standby is about 10% above prime. A set sold as "1,100 kW" may be 1,000 kW prime. When you compare quotes:
All prices we publish are quoted on the prime rating, with the standby figure shown alongside.